MinorWeilmclain boiler servicing APT 2B has boiler flue pipe in poor condition+combustion air louver is 1/2 clogged+junk in boiler room, maintain boiler; correct violation+submit certificate of correction
OATH · Filed Oct 2025 · Open
MinorBaxi boiler servicing APT 3A has safety valve in the incorrect position, maintain boiler; correct violation+submit certificate of correction
OATH · Filed Oct 2025 · Open
MinorBoiler in boiler room@apt 5A is not accessible for inspection, maintain boiler; remove junk+repair boiler room door; correct violation+submit certificate of correction
OATH · Filed Oct 2025 · Open
MinorAtoi observed deck built on the roof surface is apx 16x42 feet deck is made out of combustible material 4x4 beams and 1x4 planks. As per DOB no permit on file with the department., obtain all permits
OATH · Filed Oct 2025 · Open
Minor§ 300 M/D law file plans and application and legalize the following alteration or restore to the legal condition existing prior to the making of said alteration gas-fired boilers not venting to open air at 1st and 2nd room from south at west at public hall, 4th story
HPD · Filed Oct 2025 · Open
ClosedTakagi hot water heater servicing APT 5B is installed without a safety relief valve, maintain boiler; cease use hazardous condition correct violation immediately +call DOB 212 6020580 to lift the cease use orde
OATH · Filed Oct 2025 · Closed
ClosedBaxi boiler servicing apt#6b is inoperable+navien boiler servicing APT 6A has safety discharge pipe reduced+missing receptacle plate+both boilers missing a remote switch, maintain boiler; correct violation+subm
OATH · Filed Oct 2025 · Closed
ClosedCcb-150 boiler servicing APT 1C has the wrong safety valve installed; mawp 43.5, maintain boiler; cease use hazardous condition correct violation+call DOB 212 6020580 to lift cease use order+submit certificate o
OATH · Filed Oct 2025 · Closed